How to use the wire size calculator
- Choose what you need: size a new wire, check one you already have, or look up a gauge.
- Set the circuit: DC, AC single-phase or three-phase, and the voltage (12/24/48 V, 120/230/240 V, 208/400/480 V or your own).
- Enter the load and the one-way distance. Use amps, or watts and the calculator works out the current. The return conductor is added for you.
- Pick copper or aluminium and AWG or mm². For AWG, set the insulation and terminal ratings, the room temperature and how many current-carrying wires run together.
- Read the suggested size, the voltage drop and the voltage left at the load, which check controls, and a breaker size. Then have an electrician confirm it.
How wire size is worked out: two checks
1. Current rating (ampacity). A wire carrying more current than it is rated for runs hot. NEC Table 310.16 lists ratings for 60, 75 and 90 °C insulation at 30 °C. Hot rooms and many wires bundled together lower the rating, and the result can’t be higher than the temperature rating of the terminals it connects to. Loads that run for 3 hours or more are sized at 125%.
2. Voltage drop. Every foot of wire has resistance, so some voltage is lost on the way. On a long run the wire must be bigger than the current alone needs, so the motor, light or charger at the end still gets enough voltage.
The calculator works out both and uses the larger size. On short runs the current rating usually decides; on long or low-voltage runs, voltage drop does.
Voltage drop formula
DC and single-phase: VD = 2 × I × R × L
Three-phase: VD = √3 × I × R × L
Drop % = VD ÷ supply voltage × 100I is the current, L the one-way length and R the resistance of one conductor per foot or metre. Example: 20 A over 100 ft on 8 AWG copper (about 0.779 Ω per 1,000 ft at 75 °C): 2 × 20 × 0.779 ÷ 1,000 × 100 = 3.12 V, or 2.60% of 120 V. On 12 AWG the same run would lose 6.6%.
Short kitchen circuit
20 A · 120 V · 15 ft · copper
- Use 12 AWG on a 20 A breaker
- Drop: 0.99% — current rating controls
Same circuit, continuous load
20 A × 125% = 25 A
- Use 10 AWG on a 25 A breaker
- Loads on for 3+ hours are sized at 125%
Metric socket circuit
16 A · 230 V · 30 m · copper
- Voltage drop needs 4 mm²
- Drop: 2.30%. Check current capacity for your installation method (BS 7671 / IEC 60364)
Three-phase motor feed
15 kW · 400 V · pf 0.9 · 50 m
- Current: 24.1 A
- Voltage drop needs 4 mm² (2.87%)
- Motor circuits follow special rules (NEC Article 430, BS 7671) — use the nameplate current
Wire size by amps
Smallest copper and aluminium size by current rating alone (NEC Table 310.16, 30 °C, no more than 3 current-carrying conductors, and a standard breaker that fits). Distance is not included here — long runs need larger wire. Circuits over 100 A are terminated at 75 °C (NEC 110.14(C)(1)(b)), so the 60 °C column stops at 100 A.
| Load | Copper, 60 °C terminals | Copper, 75 °C terminals | Aluminium, 75 °C terminals |
|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 8 AWG |
| 50 A | 6 AWG | 8 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 3 AWG |
| 100 A | 1 AWG | 3 AWG | 1 AWG |
| 125 A | — (use 75 °C) | 1 AWG | 2/0 AWG |
| 150 A | — (use 75 °C) | 1/0 AWG | 3/0 AWG |
| 200 A | — (use 75 °C) | 3/0 AWG | 250 kcmil |
Wire gauge by length: how distance changes the size
Copper AWG needed to stay within 3% voltage drop, single-phase, one-way distance (current rating also checked).
| Circuit | 25 ft | 50 ft | 100 ft | 150 ft | 200 ft |
|---|---|---|---|---|---|
| 15 A @ 120 V | 14 | 12 | 8 | 8 | 6 |
| 20 A @ 120 V | 12 | 10 | 8 | 6 | 4 |
| 20 A @ 240 V | 12 | 12 | 10 | 8 | 8 |
| 30 A @ 240 V | 10 | 10 | 8 | 8 | 6 |
| 50 A @ 240 V | 8 | 8 | 6 | 4 | 4 |
12 V DC wire size (solar, RV, boat, car)
Low-voltage DC needs much thicker wire for the same current. Copper AWG to stay within 3% at 12 V, one-way distance. At 24 V you can use the column for twice the distance; at 48 V, four times. The smallest size listed is 14 AWG — very small loads can use thinner wire rated for the current. Boats should follow ABYC E-11; vehicles, the wire maker’s ratings.
| Current | 5 ft | 10 ft | 15 ft | 25 ft |
|---|---|---|---|---|
| 5 A | 14 | 14 | 12 | 10 |
| 10 A | 14 | 10 | 8 | 6 |
| 20 A | 10 | 8 | 6 | 4 |
| 30 A | 8 | 6 | 4 | 2 |
| 50 A | 6 | 4 | 2 | 1/0 |
| 100 A | 3 | 1 | 2/0 | 4/0 |
AWG vs mm²
| AWG | Area | Nearest metric up | Cu Ω/1000 ft @ 75 °C |
|---|---|---|---|
| 14 | 2.08 mm² | 2.5 mm² | 3.1327 |
| 12 | 3.31 mm² | 4 mm² | 1.9701 |
| 10 | 5.26 mm² | 6 mm² | 1.2390 |
| 8 | 8.37 mm² | 10 mm² | 0.7792 |
| 6 | 13.30 mm² | 16 mm² | 0.4901 |
| 4 | 21.15 mm² | 25 mm² | 0.3082 |
| 3 | 26.67 mm² | 35 mm² | 0.2444 |
| 2 | 33.63 mm² | 35 mm² | 0.1938 |
| 1 | 42.41 mm² | 50 mm² | 0.1537 |
| 1/0 | 53.48 mm² | 70 mm² | 0.1219 |
| 2/0 | 67.43 mm² | 70 mm² | 0.0967 |
| 3/0 | 85.03 mm² | 95 mm² | 0.0767 |
| 4/0 | 107.22 mm² | 120 mm² | 0.0608 |
AWG numbers go down as wires get thicker, and every 3 gauges roughly doubles the area. Metric cable is sold in fixed sizes, so when you convert, always round up to the next metric size. Each region has its own rules: the NEC in the US, BS 7671 in the UK, IEC 60364 across much of Europe and AS/NZS 3000/3008 in Australia and New Zealand.
Copper vs aluminium
Aluminium is lighter and cheaper but conducts about 61% as well as copper, so it needs a larger size for the same current and the same voltage drop. It also needs terminals listed for aluminium (marked AL or AL/CU) and correct torque. It is common for larger feeders and service conductors; most branch circuits in homes use copper.
Breakers, fuses and the 125% rule
The breaker or fuse protects the wire, so it must not be bigger than the wire’s allowable current — and for 14, 12 and 10 AWG copper the NEC caps it at 15, 20 and 30 A whatever the table says. For loads that run 3 hours or more, both the wire and the breaker are sized for 125% of the load. The calculator suggests the smallest standard breaker that covers the load and stays within the wire’s limit; equipment instructions and motor rules can change this.
Frequently asked questions
What size wire do I need for 30 amps?
For copper on a typical branch circuit, 10 AWG — its rating is 30 A in the 60 °C column, and 10 AWG copper may be protected at up to 30 A. Long runs need a larger wire to keep the voltage drop under 3%; enter your distance in the calculator.
What size wire do I need for 50 amps?
Copper 8 AWG where the terminals are rated 75 °C, or 6 AWG with 60 °C terminals; aluminium 6 AWG at 75 °C. Distance can push it up — a 50 A, 240 V run of 100 ft needs 6 AWG copper to stay under 3%.
What size wire do I need for 100 amps?
By current alone, 3 AWG copper or 1 AWG aluminium with 75 °C terminals. Service and feeder conductors for dwellings can be sized under special NEC rules, so a 100 A service is a job for your electrician and the local inspector.
How do you calculate voltage drop?
For DC and single-phase circuits, voltage drop = 2 × current × resistance per foot (or metre) × one-way length — the 2 counts the wire out and back. For three-phase, use √3 instead of 2. Divide by the supply voltage for the percentage.
What voltage drop is acceptable?
A common target is 3% on a branch circuit and 5% for feeder and branch together, from an informational note in the NEC. It is guidance, not a rule in most cases, but lower drop means equipment runs better. Low-voltage DC systems often aim for 2–3% or less.
What size wire for 12 V DC?
Much bigger than at 120 V, because each volt lost is a bigger share. A 20 A, 12 V load 15 ft away needs 6 AWG copper to stay within 3%; the same current at 120 V over the same distance needs only 12 AWG. Use the 12 V table on this page or the calculator.
How many amps can 14, 12 and 10 AWG copper carry?
From NEC Table 310.16 at 30 °C: 14 AWG 15/20/25 A, 12 AWG 20/25/30 A and 10 AWG 30/35/40 A in the 60/75/90 °C columns. But the breaker is limited to 15 A, 20 A and 30 A for these sizes (NEC 240.4(D)).
How do I convert AWG to mm²?
AWG area in mm² = π ÷ 4 × (0.127 mm × 92^((36 − AWG) ÷ 39))². 12 AWG is 3.31 mm² and 10 AWG is 5.26 mm². Metric cable comes in fixed sizes (1.5, 2.5, 4, 6, 10 mm²…), so round up to the next size: 12 AWG ≈ 4 mm².
Can I use aluminium wire instead of copper?
Yes, if it is rated for the job and the terminals are listed for aluminium. Aluminium conducts about 61% as well as copper, so it needs to be larger — for 100 A at 240 V over 50 ft, 1 AWG aluminium versus 3 AWG copper.
What is the difference between wire gauge and wire size in mm²?
They measure the same thing — the conductor’s cross-section — in two systems. AWG is a number where smaller means thicker; mm² is the area itself. The US uses AWG and kcmil; most of the world uses mm².
Does this calculator replace an electrician?
No. It is a planning tool. Real installations depend on the cable type, how it is installed, local code, equipment ratings and inspection. Use it to understand the numbers, then have a licensed electrician design or check the circuit.
How This Calculator Works: Formula, Defaults & Sources
Formula
- Current from power: DC I = W ÷ V; single-phase I = W ÷ (V × power factor); three-phase I = W ÷ (√3 × V × power factor)
- Voltage drop: DC and single-phase VD = 2 × I × R × L; three-phase VD = √3 × I × R × L (L = one-way length, R = resistance per length of one conductor)
- Resistance (AWG/kcmil) = resistivity at 75 °C ÷ conductor area × 1.02 for stranding; area from the AWG formula d = 0.005 in × 92^((36 − n) ÷ 39)
- Resistance (mm²) = IEC 60228 class 2 maximum at 20 °C × (1 + α × (70 − 20))
- Allowable current = NEC Table 310.16 (insulation column) × ambient factor × bundling factor, but not more than the terminal-temperature column; continuous loads × 125%
- Wire = the larger of the voltage-drop size and the current-rating size; breaker = the smallest standard rating ≥ the required current and ≤ the wire’s limit (240.4(D) for 14–10 AWG)
Default values (you can change them)
- Resistivity at 20 °C: copper 1.7241 µΩ·cm (100% IACS), α 0.00393/°C; aluminium 2.8264 µΩ·cm (61% IACS), α 0.00403/°C
- Voltage-drop limit: 3% (NEC informational note for branch circuits; not a code requirement in most cases)
- Temperature basis: AWG resistance at 75 °C (NEC Chapter 9 Table 8 basis); metric at 70 °C (PVC); ampacity table at 30 °C ambient
- Terminals: 60 °C by default (most equipment ≤ 100 A and NM-B cable), change to 75 °C for equipment marked 75 °C
- Table conflicts: where published reproductions of Table 310.16 differed (Cu 3 AWG 90 °C, Al 300 kcmil), the lower value is used
Sources
- NFPA 70, National Electrical Code — Table 310.16, Tables 310.15(B)(1) and (C)(1), 240.4(D), 240.6(A), 110.14(C), Chapter 9 Table 8 — values checked against published reproductions; verify against the edition your area adopts
- Ambient and bundling adjustment factors (Tables 310.15(B)(1) and (C)(1)) — study guide reproduction
- IEC 60228 class 2 conductor resistance — Bayka technical information
- IEC 60028 / IACS — standard annealed copper resistivity 1/58 Ω·mm²/m at 20 °C
- NIST Special Publication 811, Guide for the Use of the International System of Units — unit conversion factors (1 yd³ = 27 ft³, 1 ft = 0.3048 m, 1 lb = 0.45359237 kg)
Results are planning estimates, not engineering advice. Confirm quantities with your supplier and follow your plans and local building code. Last updated: November 15, 2026. Spotted a wrong number? Email us or use the contact page.
Related calculators
Disclaimer: results are planning estimates based on the published tables and formulas listed above. They do not cover every case (cable type, installation method, motors, reactance on large feeders, local amendments). Follow the electrical code adopted where you live and have a licensed electrician design or check the work.